GAO Jiaying, YUAN Lingyue, CHEN Yanxin, CHEN Yong, LUO Jiayuan, CHEN Mingliang, CHEN Min. Contamination status and molecular typing of Legionella pneumophila in artificial water environment in Shanghai hospitals from 2019 to 2020[J]. Journal of Environmental and Occupational Medicine, 2023, 40(7): 823-829. DOI: 10.11836/JEOM22515
Citation: GAO Jiaying, YUAN Lingyue, CHEN Yanxin, CHEN Yong, LUO Jiayuan, CHEN Mingliang, CHEN Min. Contamination status and molecular typing of Legionella pneumophila in artificial water environment in Shanghai hospitals from 2019 to 2020[J]. Journal of Environmental and Occupational Medicine, 2023, 40(7): 823-829. DOI: 10.11836/JEOM22515

Contamination status and molecular typing of Legionella pneumophila in artificial water environment in Shanghai hospitals from 2019 to 2020

Funds: This study was funded.
More Information
  • Background 

    The incidence of Legionnaires' disease is increasing globally and artificial water environment is becoming a common source of outbreaks. Molecular typing techniques can help prevent and control Legionella.

    Objective 

    To understand the molecular epidemiological characteristics of Legionella pneumophila in artificial water environment of Shanghai hospitals, and provide a scientific basis for the prevention and control of Legionnaires' disease.

    Methods 

    Water samples were collected from artificial water environment in 14 hospitals from May to October each year from 2019 to 2020 in Shanghai. A total of 984 water samples were collected from 8 Grade-A tertiary hospitals and 6 non-Grade-A tertiary hospitals, including 312 samples of cooling water, 72 samples of chilled water, and 600 samples of tap water. The water samples were isolated and serotyped for Legionella pneumophila and preserved, and the positive rate of Legionella pneumophila in the samples was used as an indicator of contamination. The preserved strains were resuscitated and 81 surviving strains were obtained for pulsed field gel electrophoresis (PFGE) typing analysis.

    Results 

    A total of 124 Legionella pneumophila positive water samples were detected, with a positive rate of 12.60%. The positive rate was higher in the Grade-A tertiary hospitals (16.54%, 87/526) than in the non-Grade-A tertiary hospitals (8.08%, 37/458) (χ2=15.91, P<0.001). The positive rate of cooling water (23.40%) was the highest among different types of water samples, and the difference was statistically significant (χ2=61.19, P<0.001). The difference in positive rate of tap water was statistically significant among different hospital departments (χ2=11.37, P<0.05). The positive rate in 2019 (15.06%) was higher than that in 2020 (9.84%) (χ2=6.23, P<0.05). From May to October, August had the highest annual average positive rate (16.46%) and October had the lowest (8.54%), but the difference in positive rates among months was not statistically significant (χ2=5.39, P=0.37). The difference in positive rate among districts was statistically significant (χ2=24.88, P<0.001). A total of 131 strains of Legionella pneumophila were isolated, with serotype 1 (80.15%, 105/131) predominating. Among the 81 surviving strains of Legionella pneumophila subjected to PFGE typing, the band-based similarity coefficients ranged from 41.30% to 100%. Among the 29 PFGE band types (S1-S29) recorded, each band type included 1-10 strains, and S28 was the dominant band type. Four clusters (I-IV) of PFGE band types were identified, accounting for 66.67% (54/81) of all strains and containing 13 band types.

    Conclusion 

    Legionella pneumophila contamination is present in the artificial water environment of hospitals in Shanghai from 2019 to 2020, and the contamination in tap water deserves attention. The detected serotype of Legionella pneumophila is predominantly type 1, and PFGE typing reveals the presence of genetic polymorphism. Therefore, the monitoring and control of Legionella pneumophila in hospital artificial water environment should be strengthened.

  • [1]
    PHIN N P, PARRY-FORD F M, HARRISON T P, et al. Epidemiology and clinical management of Legionnaires' disease[J]. Lancet Infect Dis, 2014, 14(10): 1011-1021. doi: 10.1016/S1473-3099(14)70713-3
    [2]
    LEUNG Y H, LAM C K, CHEUNG Y Y, et al. Epidemiology of Legionnaires’ disease, Hong Kong, China, 2005-2015[J]. Emerg Infect Dis, 2020, 26(8): 1695-1702. doi: 10.3201/eid2608.191244
    [3]
    BARSKEY A E, DERADO G, EDENS C. Rising Incidence of Legionnaires’ disease and associated epidemiologic patterns, United States, 1992-2018[J]. Emerg Infect Dis, 2022, 28(3): 527-538. doi: 10.3201/eid2803.211435
    [4]
    FUKUSHIMA S, HAGIYA H, OTSUKA Y, et al. Trends in the incidence and mortality of legionellosis in Japan: a nationwide observational study, 1999-2017[J]. Sci Rep, 2021, 11(1): 7246. doi: 10.1038/s41598-021-86431-8
    [5]
    QU J, ZHANG J, CHEN Y, et al. Aetiology of severe community acquired pneumonia in adults identified by combined detection methods: a multi-centre prospective study in China[J]. Emerg Microbes Infect, 2022, 11(1): 556-566. doi: 10.1080/22221751.2022.2035194
    [6]
    QIN T, REN H, CHEN D, et al. National surveillance of Legionnaires’ disease, China, 2014-2016[J]. Emerg Infect Dis, 2019, 25(6): 1218-1219. doi: 10.3201/eid2506.171431
    [7]
    SODA E A, BARSKEY A E, SHAH P P, et al. Vital signs: health care-associated Legionnaires’ disease surveillance data from 20 states and a large metropolitan area-United States, 2015[J]. Am J Transplant, 2017, 17(8): 2215-2220. doi: 10.1111/ajt.14407
    [8]
    GARRISON L E, KUNZ J M, COOLEY L A, et al. Vital signs: deficiencies in environmental control identified in outbreaks of Legionnaires’ disease - North America, 2000-2014[J]. MMWR Morb Mortal Wkly Rep, 2016, 65(22): 576-584. doi: 10.15585/mmwr.mm6522e1
    [9]
    张美彤, 董颖, 陈愉, 等. 国内军团菌病暴发病例临床特征分析[J]. 中华医院感染学杂志, 2018, 28(20): 3187-3191.

    ZHANG M T, DONG Y, CHEN Y, et al. Analysis of clinical characteristics of outbreaks of Legionnaires’ disease in China[J]. Chin J Nosocomiol, 2018, 28(20): 3187-3191.
    [10]
    VAN HEIJNSBERGEN E, SCHALK J A C, EUSER S M, et al. Confirmed and potential sources of Legionella reviewed[J]. Environ Sci Technol, 2015, 49(8): 4797-4815. doi: 10.1021/acs.est.5b00142
    [11]
    秦天, 任红宇, 周海健, 等. 中国嗜肺军团菌分离株脉冲场凝胶电泳分型分析以及数据库的建立[J]. 中华流行病学杂志, 2011, 32(3): 285-289. doi: 10.3760/cma.j.issn.0254-6450.2011.03.019

    QIN T, REN H Y, ZHOU H J, et al. Molecular typing of Legionella pneumophila isolates from China with pulsed field gel electrophoresis[J]. Chin J Epidemiol, 2011, 32(3): 285-289. doi: 10.3760/cma.j.issn.0254-6450.2011.03.019
    [12]
    孔德川, 肖文佳, 陈明亮, 等. 2011—2018年上海市公共场所人工水环境中军团菌污染情况调查及其病原型别鉴定[J]. 中华预防医学杂志, 2021, 55(1): 72-77. doi: 10.3760/cma.j.cn112150-20201122-01391

    KONG D C, XIAO W J, CHEN M L, et al. Investigation of Legionella contamination in artificial water environment of public places and identification of its pathogenic types in Shanghai from 2011 to 2018[J]. Chin J Prev Med, 2021, 55(1): 72-77. doi: 10.3760/cma.j.cn112150-20201122-01391
    [13]
    ZHOU H, REN H, ZHU B, et al. Optimization of pulsed-field gel electrophoresis for Legionella pneumophila subtyping[J]. Appl Environ Microbiol, 2010, 76(5): 1334-1340. doi: 10.1128/AEM.01455-09
    [14]
    TENOVER F C, ARBEIT R D, GOERING R V, et al. Interpreting chromosomal DNA restriction patterns produced by pulsed-field gel electrophoresis: criteria for bacterial strain typing[J]. J Clin Microbiol, 1995, 33(9): 2233-2239. doi: 10.1128/jcm.33.9.2233-2239.1995
    [15]
    张宝莹, 刘凡, 白雪涛, 等. 2009年-2014年五地区公共场所嗜肺军团菌环境污染现况调查[J]. 中国卫生检验杂志, 2016, 26(19): 2841-2843,2848.

    ZHANG B Y, LIU F, BAI X T, et al. Investigation of Legionella pneumophila contamination in public places of five districts in China from 2009 to 2014[J]. Chin J Health Lab Technol, 2016, 26(19): 2841-2843,2848.
    [16]
    万博宇, 张美云, 段杉, 等. 2018—2019年北京市朝阳区公共场所水环境中嗜肺军团菌污染状况及健康风险分析[J]. 环境卫生学杂志, 2021, 11(3): 260-264. doi: 10.13421/j.cnki.hjwsxzz.2021.03.007

    WAN B Y, ZHANG M Y, DUAN S, et al. Analysis of the contamination and health risk of Legionella Pneumophila in the water of public places in Chaoyang district of Beijing from 2018 to 2019[J]. J Environ Hyg, 2021, 11(3): 260-264. doi: 10.13421/j.cnki.hjwsxzz.2021.03.007
    [17]
    李艳丽, 杨康, 袁天明, 等. 2017-2020年十堰市公共场所嗜肺军团菌污染状况及病原学分析[J]. 职业与健康, 2022, 38(13): 1821-1824,1829. doi: 10.3969/j.issn.1004-1257.2022.13.zyyjk202213021

    LI Y L, YANG K, YUAN T M, et al. Analysis on contamination status and etiological analysis of Legionella pneumophila in public places in Shiyan City from 2017-2020[J]. Occup Health, 2022, 38(13): 1821-1824,1829. doi: 10.3969/j.issn.1004-1257.2022.13.zyyjk202213021
    [18]
    GARNER E, BROWN C L, SCHWAKE D O, et al. Comparison of whole-genome sequences of Legionella pneumophila in tap water and in clinical strains, Flint, Michigan, USA, 2016[J]. Emerg Infect Dis, 2019, 25(11): 2013-2020. doi: 10.3201/eid2511.181032
    [19]
    MENTULA S, KÄÄRIÄINEN S, JAAKOLA S, et al. Tap water as the source of a Legionnaires’ disease outbreak spread to several residential buildings and one hospital, Finland, 2020 to 2021[J]. Euro Surveill, 2023, 28(11): 2200673.
    [20]
    COOLEY L A, PONDO T, FRANCOIS W L, et al. Population-based assessment of clinical risk factors for Legionnaires’ disease[J]. Clin Infect Dis, 2020, 70(11): 2428-2431. doi: 10.1093/cid/ciz771
    [21]
    HERWALDT L A, MARRA A R. Legionella: a reemerging pathogen[J]. Curr Opin Infect Dis, 2018, 31(4): 325-333. doi: 10.1097/QCO.0000000000000468
  • Cited by

    Periodical cited type(2)

    1. 陈芳,刘洋,王剑青. 马鞍山市公共场所集中空调通风系统卫生状况影响因素分析. 职业与健康. 2024(18): 2533-2538 .
    2. 徐秦,田微微,秦铖,季星培,张伟. 南通市地铁1号线各车站集中空调通风系统微生物污染状况调查. 中国初级卫生保健. 2023(12): 93-95 .

    Other cited types(0)

Catalog

    Article views (150) PDF downloads (38) Cited by(2)

    /

    DownLoad:  Full-Size Img  PowerPoint
    Return
    Return